As some of you already know, we are moving our website from www.asteamtechnologies.com to www.asteamtechno.com as our new platform with some extra security features, optimized for Mobile view, A strong and visible call to action and many more.... Please update to your database i.e. Email addresses & web address as earliest as possible,

Thank you,
ATSPL team, Surat, India.

  • Formerly Asteam Technologies | Welcome to The Era of Automation

   +91 95378 40404

   contact@asteamtechnologies.com

Awesome Image

The ProSoft Technology’s ILX34-MBS232 module is ideal for point to point applications with a maximum distance of 50 feet away (15.2 meters) your processor. These include SCADA and field device interface applications. The module can be used in CompactLogix L1 processors or Distributed 1734 Point I/O systems. In addition, the module can be configured as a Master or Slave.


Features and Benefits
-Add-on Instruction creates UDTs, providing logical definitions for I/O, status, and control data
-Diagnostic data available in RSLogix 5000/Studio 5000 controller tags, allowing decisions to be made based upon node health -Module configuration is backed up in the CompactLogix project (ACD file)
-The serial port can be enabled or disabled through ladder logic
-Supports up to 1,000 words of data
-Supports up to 30 Modbus Commands & up to 35 words per command
-Suitable for SCADA and field device interface applications
  • Specifications
  • Configuration Environment - RSLogix 5000/Studio 5000
  • I/O Size - User selectable 16, 48, or 70 bytes
  • Communication parameters - Baud Rate: 110 to 38.4K baud, Stop Bits: 1 or 2 Data Size: 7 or 8 bits Parity: None, Even, Odd
  • Modbus Modes - RTU mode (binary) with CRC-16 ASCII mode with LRC error checking
  • Node Address - 1 to 247
  • Modbus Function Codes Supported
  • 1: Read Coil Status
  • 2: Read Input Status
  • 3: Read Holding Registers
  • 4: Read Input Registers
  • 5: Force (Write) Single Coil
  • 6: Preset (Write) Single Holding Register
  • 8: Diagnostics (Slave Only, Responds to Sub function 00)
  • 15: Force( Write) Multiple Coils
  • 16: Preset (Write) Multiple Holding Registers
Select your currency